Sku #78393689112
MFG #XCS-0S3M6G
Attributes
| Series: | XCS Series |
| Number of Poles: | 1 |
| Contact Mode: | Spring Return to Center From Right and Left |
| Voltage Rating: | 600 V AC |
| Contact Configuration: | 2NO |
| Legend: | Auto/Hand/Off |
- 60 A at 120 VAC, 30 A at 240 VAC, 15 A at 480 VAC, 12 A at 600 VAC inrush, 6 A at 120 VAC, 3 A at 240 VAC, 1.5 A at 480 VAC, 1.2 A at 600 VAC breaking, 10 A at 120 VAC, 10 A at 240 VAC and 10 A at 480 VAC carrying
- Contact blocks are rated heavy duty, 600 VAC max, internal ground screw
- Ground flange joint between bolted cover and box provide required flame path
- Push button, selector switches and pilot light operator bodies are copper-free aluminum
- Operating shaft in both push buttons and selector switches are stainless steel
- For hazardous locations due to the presence of flammable gases or vapors, combustible dusts or easily ignitable fiber or flyings, installations at petroleum refineries, chemical and petrochemical plants and other processing or storage facilities where similar hazards exist, use in conjunction with magnetic starters or contactors for remote control of motors applications
- UL File No. E53360|CSA File No. LR11714|Class I Zone 1 and 2 Groups IIB, IIA|Class II Divisions 1 and 2 Groups E, F, G|Class III