Sku #78393620076
MFG #FXCS-0S3R6G
Attributes
| Type: | Factory Sealed Standard |
| Voltage Rating: | 600 V AC |
| Contact Configuration: | 2NO |
| Series: | FXCS SEAL-X™ |
| Number of Poles: | 1 |
| Contact Mode: | Spring Return |
- For use to prevent the igniting of external hazardous atmospheres by the enclosed arcing devices in such areas as hazardous locations due to the presence of flammable gases or vapors, combustible dusts or easily ignitable fibers or flyings
- 0.55 A at 125 VDC, 0.275 A at 250 VDC inrush, 0.55 A at 125 VDC, 0.275 A at 250 VDC breaking, 2.5 A at 125/250 VDC carrying
- Color coded wiring with more wiring space for easier field installation
- Stainless steel captive screws for cover assembly
- Device covers are cast copper-free aluminum alloy
- 60 A at 120 VAC, 30 A at 240 VAC, 15 A at 480 VAC, 12 A at 600 VAC inrush, 6 A at 120 VAC, 3 A at 240 VAC, 1.5 A at 480 VAC, 1.2 A at 600 VAC breaking, 10 A at 120 VAC, 10 A at 240 VAC and 10 A at 480 VAC carrying
- Operating shaft in selector switches is stainless steel
- UL File No. E53360/E12379|CSA File No. LR11714|Class I Divisions 1 and 2 Groups C, D|Class I Zone 1 and 2 Groups IIB, IIA|Class II Divisions 1 and 2 Groups E, F, G|Class III