Sku #78393620045
MFG #FXCS-0B2
Attributes
| Type: | Factory Sealed Single |
| Voltage Rating: | 600 V AC |
| Number of Operators: | 1 |
| Series: | FXCS |
| Number of Poles: | 1 |
| Contact Configuration: | 1NC |
- For preventing the igniting of external hazardous atmospheres by the enclosed arcing devices in such areas as hazardous locations due to the presence of flammable gases or vapors, combustible dusts or easily ignitable fibers or flyings
- Elimination of external sealing requirements
- 60 A at 120 VAC, 30 A at 240 VAC, 15 A at 480 VAC, 12 A at 600 VAC inrush, 6 A at 120 VAC, 3 A at 240 VAC, 1.5 A at 480 VAC, 1.2 A at 600 VAC breaking, 10 A at 120 VAC, 10 A at 240 VAC, 10 A at 480 VAC carrying contact rating
- NEMA 3 weatherproof
- Color coded wiring with more wiring space for easier field installation
- Stainless steel captive screws for cover assembly
- Ground boss for grounding in the splice box
- Operating shaft in both pushbuttons and selector switches are stainless steel
- Pushbutton, selector switches and pilot light bodies are copper-free aluminum
- Lockout accessory available must be factory installed
- UL File No. E53360/E12379|CSA File No. LR11714, Class I Divisions 1 and 2 Groups C, D Class I Zones 1 and 2 Groups IIB, IIA Class II Divisions 1 and 2 Groups E, F, G Class III